Its 100 kA breaking capacity at 400 V AC (and across the 240–690 V AC range) means it can safely interrupt high fault currents without upstream fuses in most industrial panel designs — a key spec for SCCR coordination. Trip Class 10 matches the thermal characteristics of standard induction motors, tripping within 10 seconds at 7.2× rated current.
The 45 mm width and 97 mm depth fit standard S0 panel layouts; any mounting position is acceptable. Clearance: 50 mm above and below, 30 mm at the sides, zero forwards or backwards — tight panel integration is straightforward. Spring-loaded terminals accept 2× (1–10 mm²) solid or stranded wire — no lug crimping, just strip and insert. Screwdriver shaft diameter 3 mm, tip 3.0 × 0.5 mm for the terminal actuation.