Motor Protection Circuit Breaker for Panel Integration
Ground fault detection is not included — this is a standard motor-only protector, not a combined GFCI device.
Width is 45 mm — a single modular DIN-rail space — with 97 mm depth and height. Main contact terminals accept M4 screws; wire range is 2× (1 to 2.5 mm²) or 2× (2.5 to 10 mm²) solid or stranded. Screwdriver shaft diameter 5 to 6 mm for the terminal screws. Mounting position is any orientation, so vertical or horizontal DIN-rail placement works without derating the thermal trip curve.
Ratings and Operating Conditions
Rated insulation voltage spans 20 to 690 V. Breaking capacity holds at 100 kA across 240 V, 400 V, 500 V, and 690 V AC. At 480 V the rated current is 1.6 A; at 600 V also 1.6 A. Horsepower ratings: 0.1 hp at 230 V, 1 hp at 460/480 V, 0.8 hp at 575/600 V. Maximum switching frequency under AC-3 duty is 15 operations per hour.