Rated 2 A at 480 V and 2 A at 600 V, it delivers 100 kA SCCR at 400 V and 240 V — enough to coordinate with most downstream contactors in a standard MCC lineup. The spring-loaded terminals accept 2x 0.5…2.5 mm² solid or stranded, and the breaker mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 60715. Ground fault detection is not included; if ground-fault protection is required, add a separate RCD or GFCI module upstream.
Minimum clearance to adjacent components: 50 mm upwards, 50 mm downwards, 30 mm at the side, and 0 mm forwards and backwards — meaning it can be mounted flush against the back panel and enclosure door, saving rail space in a tight cabinet.
Switching capacity and auxiliary contacts
Auxiliary contact ratings: 1 A at 24 V, 0.5 A at 120 V/125 V/230 V, and 0.15 A at 60 V — these are the current-carrying limits for the built-in auxiliary switch, not the main motor circuit. The main circuit is rated for 100 kA SCCR at 240 V, 400 V, and 500 V, dropping to 10 kA at 690 V. Maximum switching frequency is 15 operations per hour under AC-3 and AC-3e duty — fine for a pump or fan cycling a few times an hour, not for a high-cycle conveyor.