The 3RV2021-1CA10: Its CLASS 10 trip class means it will trip within 10 seconds at 7.2× the thermal setting, which is the standard for protecting standard induction motors during start-up — it lets the motor accelerate without nuisance tripping on inrush.
Main circuit terminals are M4 screw-type, accepting 2×(1…2.5 mm²) or 2×(2.5…10 mm²) solid or stranded copper. Keep the strip length clean to avoid stray strands under the screw head. Clearance: 50 mm above and below, 30 mm to the side, 0 mm forward or backward — so you can pack it tight front-to-back in a shallow enclosure.
Short-circuit ratings — what they mean for coordination
Rated short-circuit breaking capacity is 100 kA at 240 V, 400 V, and 500 V AC, dropping to 10 kA at 690 V AC.
The 3RV2021-1CA10 is a drop-in replacement for panels designed around the SIRIUS 3RV2 family.