Clearance requirements: 50 mm above and below, 30 mm to the side, zero forward or backward — so it fits tight against a backpanel or gland plate as long as vertical airflow is respected.
Breaking capacity across voltage levels
Breaking capacity is voltage-dependent: 100 kA at 240 V and 400 V AC, dropping to 10 kA at 690 V. This is a motor-protective device, not a general-purpose distribution breaker — the 100 kA rating at 400 V means it can be installed on a high-fault panel without requiring an upstream current-limiting fuse, as long as the motor full-load current falls within the adjustable thermal range.
Environmental and operational limits
Rated for operation between -20 °C and +60 °C with temperature compensation active across that same span. Storage and transport range extends from -50 °C to +80 °C. Any mounting position is acceptable. The unit includes phase failure detection but no ground fault detection — if ground fault protection is required on the motor circuit, it must be added externally via a separate module or upstream device.
Lifecycle stage is listed as current, meaning the manufacturer has not issued a phase-out notice.