Motor protection with Class 10 trip and phase failure detection
The breaker is rated for a 100 kA breaking capacity at 400 V AC and 500 V AC, and 10 kA at 690 V — high enough to handle most industrial fault-current scenarios without requiring an upstream current-limiting fuse for SCCR compliance.
Mounting and wiring for panel integration
Depth is 97 mm, height 119 mm. Clearance requirements: 50 mm upward, 50 mm downward, 30 mm at the side; zero forward or backward clearance needed. That side clearance is tighter than many breakers — useful when packing multiple units side-by-side in a crowded enclosure.
The lifecycle stage is listed as current, meaning the manufacturer continues to produce and support this order code. No successor has been assigned.