Siemens 3RV2021-1GA20-0BA0 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2021-1GA20-0BA0 SIRIUS Motor Protection Circuit B

MPN3RV2021-1GA20-0BA0
Active

Siemens SIRIUS 3RV2021-1GA20-0BA0 motor protection circuit breaker, size S0, Class 10 trip, 6.3 A at AC-3 400 V, 100 kA breaking capacity at 400 V, spring-loaded terminals, screw and snap-on DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV2021-1GA20-0BA0 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS0

Electrical

3RV2021-1GA20-0BA0 — Electrical
ParameterValue
Rated operational current (Ie)6.3 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W

Protection & Tripping

3RV2021-1GA20-0BA0 — Protection & Tripping
ParameterValue
Overload release setting range4.5 ... 6.3 A
Instantaneous short-circuit trip current82 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)6 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V4 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes

Endurance & Switching

3RV2021-1GA20-0BA0 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)500
Endurance, auxiliary contacts (typ.)500
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0

Connections

3RV2021-1GA20-0BA0 — Connections
ParameterValue
Main-circuit terminal typespring-loaded terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (1 ... 10 mm²)
Conductor cross-section, finely stranded with ferrule2x (1 ... 6 mm²)

Mechanical

3RV2021-1GA20-0BA0 — Mechanical
ParameterValue
Height119 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
Mounting positionany

Environmental

3RV2021-1GA20-0BA0 — Environmental
ParameterValue
Operating temperature-50 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m

Specifications

3RV2021-1GA20-0BA0 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

Motor protection circuit breaker, size S0, Class 10, 6.3 A AC-3

The Siemens SIRIUS 3RV2021-1GA20-0BA0 is a motor protection circuit breaker designed for the main current circuit of three-phase motors. It is part of the SIRIUS family and comes in the compact S0 frame size (45 mm wide, 97 mm deep, 119 mm high). The breaker is rated for AC-3 duty at 6.3 A at 400 V, with a trip class of CLASS 10, meaning it will trip within 10 seconds at 7.2× the thermal setting — fast enough to protect standard induction motors during locked-rotor conditions. Breaking capacity is 100 kA at 240 V, 400 V, and 500 V AC, dropping to 6 kA at 690 V AC. That 100 kA figure at 400 V means it can safely interrupt a fault current up to 100,000 amps without welding contacts or cascading failure upstream — critical for panels with high available fault current from large transformers. Phase failure detection is built in, so if one phase drops out, the breaker trips before single-phasing cooks the motor. No ground fault detection on this variant.

Mounting and wiring

Mounts via screw and snap-on onto 35 mm standard mounting rail per DIN EN 60715. Any mounting position is allowed. The main current circuit uses spring-loaded terminals accepting 2× (1–10 mm²) solid or stranded wire. That spring-cage design speeds up panel wiring — no screw torque to check, just strip and push. Clearance distances: 50 mm upwards and downwards, 30 mm to the side, zero forwards or backwards. That 50 mm top clearance is the one to watch when stacking breakers in a row — leave room for the arc chute to vent.

MPN
3RV2021-1GA20-0BA0