Skip to main content
Siemens 3RV2021-1HA10-ZW96 — Motor Protection Circuit Breakers (MPCB)

Siemens SIRIUS 3RV2021-1HA10-ZW96 Motor Protection Circuit B

MPN3RV2021-1HA10-ZW96
Active

Siemens SIRIUS motor protection circuit breaker, 3RV2021-1HA10-ZW96, Trip Class 10, 100 kA breaking capacity at 400 V, 45 mm width, screw and snap-on mounting on 35 mm DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV2021-1HA10-ZW96 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS0
3RV2021-1HA10-ZW96 — Electrical
ParameterValue
Rated operational current (Ie)8 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)9.25 W
Power loss, per pole (AC, hot)3.1 W
3RV2021-1HA10-ZW96 — Protection & Tripping
ParameterValue
Overload release setting range5.5 ... 8 A
Instantaneous short-circuit trip current104 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)42 kA
Breaking capacity at 690 V (AC)6 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V4 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2021-1HA10-ZW96 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0
3RV2021-1HA10-ZW96 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (1 ... 2.5 mm²), 2x (2.5 ... 10 mm²)
Conductor cross-section, finely stranded with ferrule2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²), 1x 10 mm²
3RV2021-1HA10-ZW96 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2021-1HA10-ZW96 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2021-1HA10-ZW96 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

Motor protection circuit breaker for panel integration

Breaking capacity and voltage ratings

This breaker delivers 100 kA breaking capacity at 240 V and 400 V AC, dropping to 42 kA at 500 V and 4 kA at 690 V. At 480 V and 600 V the rated current is 8 A. These ratings cover most industrial motor branch circuits in North American and European voltage systems.

Clearance requirements: 50 mm upwards and downwards, 30 mm at the side, 0 mm forwards and backwards. Screw-type terminals for the main current circuit accept solid or stranded conductors: 2x (1…2.5 mm²) and 2x (2.5…10 mm²).

Frequently asked questions

Where can I buy 3RV2021-1HA10-ZW96?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3RV2021-1HA10-ZW96 at 400 V?

The breaking capacity at 400 V AC is 100 kA.

What are the mounting clearances for 3RV2021-1HA10-ZW96?

Clearance requirements: 50 mm upwards and downwards, 30 mm at the side, 0 mm forwards and backwards.

MPN
3RV2021-1HA10-ZW96