Motor protection circuit breaker for Class 10 coordination
Rated interrupting capacity reaches 100 kA at both 240 V and 400 V AC, so it can be applied on high-fault-capacity distribution panels without requiring upstream current-limiting fuses.
For a panel originally specified around the 3RV2021-1GA15, the 3RV2021-1HA10-ZX95 shares the same 45 mm footprint and DIN-rail mounting, so it drops in without rewiring or enclosure modifications. The functional difference is in the trip setting range and interrupting ratings — verify those against your motor FLA before substituting.
Integration note
Screw-type terminals on the main circuit accept 2x (1–2.5 mm²) solid/stranded or 2x (2.5–10 mm²). The M4 contact screws are standard for panel wiring.