Width is 45 mm, depth 97 mm, height 119 mm. Clearance requirements: 50 mm upwards and downwards, 30 mm to the side, zero forwards or backwards. The zero forward clearance means it can be mounted flush against a panel door or backplate without additional standoffs.
Termination and environment
Spring-cage termination speeds panel wiring — no torque driver needed, and the connection stays vibration-resistant in a motor-starting environment.
Protection features
Ground fault detection is not integrated, so if ground-fault protection is required it must be added externally. Maximum switching frequency at AC-3 duty is 15 operations per hour, which suits pump, fan, and conveyor cycling but not high-speed jogging or reversing applications.