Clearance requirements: 50 mm above and below, 30 mm to the side, zero forward or backward. Any mounting position is permitted.
Termination and wiring
Main circuit terminals are M4 screw-type, accepting 2x (1 to 2.5 mm²) or 2x (2.5 to 10 mm²) solid or stranded copper. The dual-wire capacity is useful for daisy-chaining power through the breaker to a downstream contactor without an extra terminal block.