Siemens 3RV2021-4BA10-ZX95 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2021-4BA10-ZX95 SIRIUS Motor Protection Circuit B

MPN3RV2021-4BA10-ZX95
Active

Siemens SIRIUS 3RV2021-4BA10-ZX95 motor protection circuit breaker, Class 10 trip, 45 mm wide, screw and snap-on mounting on 35 mm DIN rail.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV2021-4BA10-ZX95 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS0

Electrical

3RV2021-4BA10-ZX95 — Electrical
ParameterValue
Rated operational current (Ie)20 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)10.5 W
Power loss, per pole (AC, hot)3.5 W

Protection & Tripping

3RV2021-4BA10-ZX95 — Protection & Tripping
ParameterValue
Overload release setting range13 ... 20 A
Instantaneous short-circuit trip current260 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)55 kA
Breaking capacity at 500 V (AC)10 kA
Breaking capacity at 690 V (AC)4 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V2 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes

Endurance & Switching

3RV2021-4BA10-ZX95 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0

Connections

3RV2021-4BA10-ZX95 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (1 ... 2.5 mm²), 2x (2.5 ... 10 mm²)
Conductor cross-section, finely stranded with ferrule2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²), 1x 10 mm²
Conductor range, AWG (main contacts)2x (16 ... 12), 2x (14 ... 8)

Mechanical

3RV2021-4BA10-ZX95 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
Mounting positionany

Environmental

3RV2021-4BA10-ZX95 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m

Specifications

3RV2021-4BA10-ZX95 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

The Siemens SIRIUS 3RV2021-4BA10-ZX95 is a motor-protection circuit breaker with Trip Class 10. It mounts on a 35 mm DIN rail per EN 60715, fits a 45 mm wide slot, and includes phase failure detection.

Short-circuit ratings and selectivity

The interrupting capacity varies with line voltage: 100 kA at 240 V, 25 kA at 400 V, 5 kA at 500 V, and 2 kA at 690 V. At 400 V the gL/gG fuse backup rating is 63 A; at 500 V and 690 V it drops to 50 A. These figures govern the upstream fuse or breaker selection for selective coordination — the 25 kA at 400 V covers most industrial distribution panels, but the 2 kA at 690 V means the breaker alone cannot clear a high-fault bolted short on a 690 V bus without an upstream current-limiting device.

Mounting and clearances

The breaker measures 97 mm deep by 45 mm wide by 97 mm tall. Required free space around the enclosure: 50 mm above and below, 30 mm to the sides, and zero forward or backward clearance — so it can be stacked tight against the back panel or a rear busbar. The screw-type terminals accept 2×(1…2.5 mm²) or 2×(2.5…10 mm²) solid or stranded copper; the main contact screws are M4. Operating temperature range is -20 to +60 °C; storage and transport range is -50 to +80 °C.

MPN
3RV2021-4BA10-ZX95