Screw-type terminals on the main current circuit accept 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid or stranded conductors, with M4 screws for the main contacts.
Rated short-circuit breaking capacity varies with line voltage: 100 kA at 240 V, 25 kA at 400 V, 5 kA at 500 V, and 2 kA at 690 V. At 400 V the gL/gG fuse backup rating is 63 A; at 500 V and 690 V it drops to 50 A. For a panel designer coordinating with upstream fuses or a molded-case breaker, these numbers define the selectivity window — the 25 kA at 400 V covers most industrial distribution systems without requiring a current-limiting upstream device.