Breaking capacity at 400 V is 25 kA — sufficient for most industrial panel bus feeds up to that fault level without requiring an upstream current-limiting fuse or backup MCCB. The 45 mm width (three 15 mm modular spaces) fits standard panel layout grids. Spring-loaded terminals on the main circuit accept 2× (0.5 to 2.5 mm²) solid or stranded — no screw torque to verify, which speeds wiring on repetitive builds.
Compliance documentation for this series includes CE marking, UL/CSA recognition, and RoHS/REACH declarations. Certificates are available on request.