Trip Class 10 and interrupting capacity
DIN rail fit and wiring
Any mounting position is permitted, so it fits in tight enclosures where the rail is vertical or inverted. Main circuit terminals accept solid or stranded copper: 2×(1…2.5 mm²) or 2×(2.5…10 mm²) per clamp. The M4 screw terminals are the same across the SIRIUS 3RV2 family, so a panel builder can standardise on one torque driver for the whole lineup. Clearance dimensions: 70 mm upwards and downwards, 30 mm to the side, 0 mm forwards — the breaker can sit flush against a panel door or adjacent component without derating.