Motor protection circuit breaker, size S0
The interrupting ratings are what you need for coordination studies: 100 kA at 240 V, 10 kA at 400 V, 3 kA at 500 V, and 2 kA at 690 V. That 10 kA at 400 V covers most industrial panelboard fault levels without needing upstream current-limiting fuses. Width is 45 mm.
The S0 frame accepts screw-type terminals sized for 2×(1…2.5 mm²) or 2×(2.5…10 mm²) solid or stranded copper. Terminal screws are M4, requiring a Pozidriv size 2 tip or a 5–6 mm diameter screwdriver shaft. Clearance requirements: 70 mm upward and downward, 30 mm at the sides, zero forward or backward. Rated operational voltage covers 20…690 V. Maximum switching frequency at AC-3 duty is 15 operations per hour.
Protection features
Ground fault detection is not integrated; that requires an external module or a separate ground-fault relay.