Skip to main content
Siemens 3RV2031-4BA10-ZX95 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2031-4BA10-ZX95 SIRIUS Motor Protection Circuit B

MPN3RV2031-4BA10-ZX95

Siemens SIRIUS motor protection circuit breaker, 3RV2031-4BA10-ZX95, CLASS 10 trip, 100 kA breaking capacity at 240 V, 55 x 140 x 149 mm, screw and snap-on 35 mm DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RV2031-4BA10-ZX95 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS2
3RV2031-4BA10-ZX95 — Electrical
ParameterValue
Rated operational current (Ie)20 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)14.5 W
Power loss, per pole (AC, hot)4.8 W
3RV2031-4BA10-ZX95 — Protection & Tripping
ParameterValue
Overload release setting range14 ... 20 A
Instantaneous short-circuit trip current260 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)65 kA
Breaking capacity at 500 V (AC)12 kA
Breaking capacity at 690 V (AC)5 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V3 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2031-4BA10-ZX95 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)50 000
Endurance, auxiliary contacts (typ.)50 000
Switching frequency, AC-3 (max.)15 1/h
3RV2031-4BA10-ZX95 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (1 ... 25 mm²), 1x (1 ... 35 mm²)
Conductor cross-section, finely stranded with ferrule2x (1 ... 16 mm²), 1x (1 ... 25 mm²)
3RV2031-4BA10-ZX95 — Mechanical
ParameterValue
Height140 mm
Width55 mm
Depth149 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2031-4BA10-ZX95 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2031-4BA10-ZX95 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

The Siemens SIRIUS 3RV2031-4BA10-ZX95 is a motor protection circuit breaker designed for Class 10 trip response, meaning it will disconnect within 10 seconds at 7.2× the thermal setting — fast enough to protect standard induction motors during locked-rotor events without nuisance tripping on normal starts. Breaking capacity is 100 kA at 240 V, 30 kA at 400 V, 6 kA at 500 V, and 3 kA at 690 V — the 400 V figure is the one that governs most European 400 V line-side installations, and it provides ample SCCR headroom for typical panel coordination.

This part carries a lifecycle status of current production, so it remains available through the standard Siemens SIRIUS channel.

Key Protection Features

Ground fault detection is not included, so if that is required, an external ground-fault module or a different SIRIUS variant would be needed. Rated operational voltage spans 20 to 690 V, covering low-voltage motor circuits from 24 V control transformers up to 690 V industrial mains.

Dimensions are 55 mm wide, 140 mm high, 149 mm deep — a standard SIRIUS 3RV2 footprint that fits alongside contactors and overloads on the same DIN rail. Main circuit terminals accept screw-type connections: 2× (1 to 25 mm²) or 1× (1 to 35 mm²) solid or stranded, with M6 terminal screws. Maximum switching frequency in AC-3 duty is 15 operations per hour, which suits motor starting cycles for pumps, fans, and compressors — not high-speed jogging or reversing applications.

Frequently asked questions

What is the breaking capacity of 3RV2031-4BA10-ZX95 at 400 V?

30 kA at 400 V, which is the key rating for most European 400 V line-side installations and provides strong SCCR headroom for panel coordination.

Will 3RV2031-4BA10-ZX95 drop into a panel specified around 3RV1011-1HA10?

The 3RV2031 is a physically larger frame (55 mm wide vs the 3RV1011's 45 mm) with higher breaking capacities, so it will not drop in without checking DIN rail space and terminal clearances. The 3RV1011 is a different SIRIUS frame size and is not a direct mechanical substitute.

How do I get current pricing and availability for 3RV2031-4BA10-ZX95?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability confirmation at quote time.

MPN