Siemens 3RV2031-4BA15 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2031-4BA15 SIRIUS Motor Protection Circuit Breake

MPN3RV2031-4BA15
Active

Siemens SIRIUS motor protection circuit breaker, 3RV2031-4BA15, Class 10 trip, 30 kA breaking capacity at 400 V AC, screw and snap-on mounting onto 35 mm DIN rail (DIN EN 60715).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RV2031-4BA15 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS2
3RV2031-4BA15 — Electrical
ParameterValue
Rated operational current (Ie)20 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)14.5 W
Power loss, per pole (AC, hot)4.8 W
3RV2031-4BA15 — Protection & Tripping
ParameterValue
Overload release setting range14 ... 20 A
Instantaneous short-circuit trip current260 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)65 kA
Breaking capacity at 500 V (AC)12 kA
Breaking capacity at 690 V (AC)5 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V3 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2031-4BA15 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)50 000
Endurance, auxiliary contacts (typ.)50 000
Switching frequency, AC-3 (max.)15 1/h
3RV2031-4BA15 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (18 ... 3), 1x (18 ... 2)
3RV2031-4BA15 — Mechanical
ParameterValue
Height140 mm
Width55 mm
Depth149 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2031-4BA15 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2031-4BA15 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

Trip Class 10 means it clears a locked-rotor condition within 10 seconds at the set overload current — fast enough for most standard induction motor starts without nuisance tripping. Breaking capacity is 30 kA at 400 V AC, with higher values at lower voltages (100 kA at 240 V) and lower at 500 V (6 kA) and 690 V (3 kA).

Dimensions: 149 mm depth, 55 mm width, 140 mm height. The 55 mm width is three 18 mm module spaces — standard for a motor-protective device in a distribution board. Mounting position is any; clearance above and below is 50 mm, 10 mm at the sides.

Frequently asked questions

Does 3RV2031-4BA15 detect phase failure?

Yes, phase failure detection is built in — the breaker will trip if one phase drops out, protecting the motor from single-phasing.

MPN
3RV2031-4BA15