Trip Class 20 means it allows a 20-second cold-start acceleration time before tripping — sized for standard induction motors driving pumps, fans, or conveyors that need a few seconds to spin up. Rated operating voltage spans 20 to 690 V AC, covering 400 V distribution common in industrial panels.
At 400 V the 3RV2031-4BB15 interrupts 30 kA; at 690 V that drops to 3 kA.
Width is 55 mm, depth 149 mm, height 140 mm — fits a standard 55 mm-wide slot on a DIN rail, leaving 10 mm clearance at the side and 50 mm above and below for airflow and wiring. Main contact terminals accept 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid or stranded wire; M6 screw for the main contacts.