The 55 mm width and 149 mm depth fit standard panel layouts; clearance requirements are 50 mm upward, 50 mm downward, and 10 mm to the side — no extra space needed forward or backward.
Integration Notes
Screw-type terminals on the main circuit accept 2×(1–25 mm²) or 1×(1–35 mm²) solid or stranded copper. Terminal size M6 for the main contacts. Temperature compensation is active across the -20 to +60 °C operating range. Maximum switching frequency under AC-3 duty is 15 operations per hour — adequate for motor starting applications but not for high-cycling loads like rapid reversing or jogging. For higher duty cycles, consider a contactor with a higher mechanical life rating.