No ground fault detection here; that's handled separately if needed. Rated operating voltage spans 20 to 690 V AC, covering most industrial motor voltages from 208 V to 600 V. Interrupting capacity is substantial: 100 kA at 240 V, 30 kA at 400 V, 4 kA at 500 V, and 2 kA at 690 V. At 480 V it carries 52 A continuous, and at 600 V also 52 A. Motor horsepower ratings run from 5 hp at 110/120 V up to 50 hp at 575/600 V.
Width is 55 mm — a standard 3-module footprint for this class of motor-protective device. Depth is 149 mm, height 140 mm. Clearance requirements: 50 mm upwards, 50 mm downwards, 10 mm at the side — but at 400 V and above, the upward clearance jumps to 160 mm, at 500 V to 125 mm, at 690 V to 100 mm. At 240 V no additional clearance is needed. Terminal size is M6. That's enough for the 52 A rating with some headroom; a 50 mm² lug is comfortable.