Skip to main content
Siemens 3RV2031-4WB10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2031-4WB10 SIRIUS Motor Protection Circuit Breake

MPN3RV2031-4WB10
Active

Siemens SIRIUS motor protection circuit breaker, 3RV2031-4WB10, Class 20 trip, 30 kA breaking capacity at 400 V, screw-type terminals, screw and snap-on mounting onto 35 mm DIN rail.

$134.62Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV2031-4WB10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS2
3RV2031-4WB10 — Electrical
ParameterValue
Rated operational current (Ie)52 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)24.5 W
Power loss, per pole (AC, hot)8.2 W
3RV2031-4WB10 — Protection & Tripping
ParameterValue
Overload release setting range42 ... 52 A
Instantaneous short-circuit trip current741 A
Trip classCLASS 20
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)65 kA
Breaking capacity at 500 V (AC)8 kA
Breaking capacity at 690 V (AC)4 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V2 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2031-4WB10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)50 000
Endurance, auxiliary contacts (typ.)50 000
Switching frequency, AC-3 (max.)15 1/h
3RV2031-4WB10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (1 ... 35 mm²), 1x (1 ... 50 mm²)
Conductor cross-section, finely stranded with ferrule2x (1 ... 25 mm²), 1x (1 ... 35 mm²)
Conductor range, AWG (main contacts)2x (18 ... 2), 1x (18 ... 1)
3RV2031-4WB10 — Mechanical
ParameterValue
Height140 mm
Width55 mm
Depth149 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2031-4WB10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2031-4WB10 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

Clearance distances are tight: 50 mm above and below, 10 mm at the sides — no extra gap at 240 V, but at 400 V you need 160 mm above, 125 mm at 500 V, and 100 mm at 690 V.

Termination and ratings

Main circuit terminals are screw-type, accepting 2x 1–35 mm² or 1x 1–50 mm² solid or stranded copper. The M6 main contact bolts are standard for this frame size. Rated operational voltage spans 20 to 690 V. Maximum switching frequency in AC-3 duty is 15 operations per hour — fine for a pump or conveyor start, not for a jogging application.

Frequently asked questions

Where can I buy 3RV2031-4WB10 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ with your target quantity for a firm response.

What clearance distances does 3RV2031-4WB10 need above and below?

50 mm above and below, with 10 mm at the sides. At 400 V the required upward clearance increases to 160 mm; at 500 V it is 125 mm; at 690 V it is 100 mm. No additional clearance is needed at 240 V.

What is the breaking capacity of 3RV2031-4WB10 at 400 V?

30 kA at 400 V. At 240 V it is 100 kA, at 500 V it is 4 kA, and at 690 V it is 2 kA. The 30 kA at 400 V is the rating that governs most industrial panel SCCR calculations.

Does 3RV2031-4WB10 include phase failure protection?

Yes, phase failure detection is built in. Ground fault detection is not included.

MPN
3RV2031-4WB10