Skip to main content
Siemens 3RV2032-4KA10-ZX95 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2032-4KA10-ZX95 SIRIUS Motor Protection Circuit B

MPN3RV2032-4KA10-ZX95

Siemens SIRIUS motor protection circuit breaker, 3RV2032-4KA10-ZX95, CLASS 10, for motor protection, screw and snap-on mounting onto 35 mm DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RV2032-4KA10-ZX95 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS2
3RV2032-4KA10-ZX95 — Electrical
ParameterValue
Rated operational current (Ie)73 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)29.5 W
Power loss, per pole (AC, hot)9.8 W
3RV2032-4KA10-ZX95 — Protection & Tripping
ParameterValue
Overload release setting range62 ... 73 A
Instantaneous short-circuit trip current949 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)10 kA
Breaking capacity at 690 V (AC)6 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V4 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2032-4KA10-ZX95 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)20 000
Endurance, auxiliary contacts (typ.)20 000
Switching frequency, AC-3 (max.)15 1/h
3RV2032-4KA10-ZX95 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (1 ... 35 mm²), 1x (1 ... 50 mm²)
Conductor cross-section, finely stranded with ferrule2x (1 ... 25 mm²), 1x (1 ... 35 mm²)
3RV2032-4KA10-ZX95 — Mechanical
ParameterValue
Height140 mm
Width55 mm
Depth149 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2032-4KA10-ZX95 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2032-4KA10-ZX95 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

It snaps onto 35 mm DIN rail per DIN EN 60715 and accepts screw-type terminals on the main circuit — rated for 2x 1…35 mm² or 1x 1…50 mm² solid or stranded conductors, with M6 main contact bolts.

Breaking capacity and trip class

Phase failure detection and ambient range

Built-in phase failure detection is standard — if one line drops, the breaker trips, preventing single-phasing damage. No ground-fault detection on this variant, so plan a separate GF module if the application requires it.

Mounting clearances and dimensions

Dimensions are 55 mm wide, 140 mm high, 149 mm deep. Mounting position is unrestricted, which helps in tight retrofit enclosures.

Frequently asked questions

Where can I buy 3RV2032-4KA10-ZX95?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3RV2032-4KA10-ZX95 at 400 V?

Rated breaking capacity is 50 kA at 400 V, with 100 kA at 240 V and 8 kA at 500 V.

What are the mounting clearances for this breaker?

Clearances required: 50 mm upwards and downwards, 10 mm at the sides, zero forward and backward. Mounting position is unrestricted.

MPN
3RV2032-4KA10-ZX95