Skip to main content
Siemens 3RV2032-4PA15 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2032-4PA15 SIRIUS Motor Protection Breaker, 100 k

MPN3RV2032-4PA15
Active

Siemens SIRIUS motor protection circuit breaker, 3RV2032-4PA15, Trip Class 10, 100 kA breaking capacity at 240 V, 50 kA at 400 V, screw and snap-on mounting onto 35 mm DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV2032-4PA15 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS2
3RV2032-4PA15 — Electrical
ParameterValue
Rated operational current (Ie)36 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)20 W
Power loss, per pole (AC, hot)6.7 W
3RV2032-4PA15 — Protection & Tripping
ParameterValue
Overload release setting range28 ... 36 A
Instantaneous short-circuit trip current520 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)15 kA
Breaking capacity at 690 V (AC)6 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V4 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2032-4PA15 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)50 000
Endurance, auxiliary contacts (typ.)50 000
Switching frequency, AC-3 (max.)15 1/h
3RV2032-4PA15 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
3RV2032-4PA15 — Mechanical
ParameterValue
Height140 mm
Width55 mm
Depth149 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2032-4PA15 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2032-4PA15 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

Motor protection circuit breaker for 3-phase loads

It combines a thermal overload relay and a magnetic short-circuit release in one DIN-rail-mounted package.

Rated breaking capacity hits 100 kA at 240 V, 50 kA at 400 V, and 4 kA at 690 V. That 50 kA at 400 V covers most industrial service-entrance fault levels — you can place this breaker close to the transformer without worrying about upstream coordination.

Width is 55 mm — fits a standard 3-module footprint. Any mounting position is acceptable, so you can lay it sideways in a shallow gland plate if needed.

Frequently asked questions

What are the key ratings for 3RV2032-4PA15?

Trip Class 10, breaking capacity 100 kA at 240 V and 50 kA at 400 V, phase failure detection included. Width 55 mm, depth 149 mm, height 140 mm. Mounts on 35 mm DIN rail.

Will 3RV2032-4PA15 drop into a panel specified around 3RV2021-4NA25?

Both are SIRIUS motor protection breakers on the same DIN rail footprint, but the 3RV2032-4PA15 is physically larger (55 mm wide vs the 3RV2021 frame's 45 mm). Verify panel space and busbar spacing before swapping — the 3RV2032 series carries higher breaking capacities and may need more clearance.

Where can I buy 3RV2032-4PA15 and how is it quoted?

This part is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — quotes are confirmed at the time of request.

MPN
3RV2032-4PA15