Skip to main content
Siemens 3RV2041-4HA15 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2041-4HA15 SIRIUS Motor Protection Circuit Breake

MPN3RV2041-4HA15
Active

Siemens SIRIUS 3RV2041-4HA15, motor protection circuit breaker, Class 10, 30 kA at 400 V, screw terminals, 35 mm DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RV2041-4HA15 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS3
3RV2041-4HA15 — Electrical
ParameterValue
Rated operational current (Ie)50 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 31 000 V
Rated impulse withstand voltage (Uimp)8 kV
Number of poles3
Power loss (AC, hot)27 W
Power loss, per pole (AC, hot)9 W
3RV2041-4HA15 — Protection & Tripping
ParameterValue
Overload release setting range36 ... 50 A
Instantaneous short-circuit trip current650 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)65 kA
Breaking capacity at 500 V (AC)12 kA
Breaking capacity at 690 V (AC)6 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V3 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2041-4HA15 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)25 000
Endurance, auxiliary contacts (typ.)25 000
Switching frequency, AC-3 (max.)15 1/h
3RV2041-4HA15 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (2,5 ... 50 mm²), 1x (10 ... 70 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
3RV2041-4HA15 — Mechanical
ParameterValue
Height165 mm
Width70 mm
Depth176 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2041-4HA15 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2041-4HA15 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

It combines a disconnect switch, a thermal overload relay, and a magnetic short-circuit release in one package, sized to protect a motor against overload, phase failure, and short circuit. That's fast enough to keep the windings from cooking on a stalled rotor but slow enough to let the motor accelerate normally under load.

Breaking capacity — the real-world number

Any mounting position is allowed, which helps when you're fitting it into a tight corner of an existing panel. The 70 mm width and 176 mm depth are the numbers to check for gland-plate clearance and door-swing interference. That's one less relay to wire and one less thing to fail out here in the grease.

Frequently asked questions

What is the breaking capacity of the 3RV2041-4HA15 at 400 V?

It is rated at 30 kA at 400 VAC. At 240 VAC it handles 100 kA, and at 690 VAC it drops to 3 kA.

Where can I buy the 3RV2041-4HA15 and how is it quoted?

This part is sourced through our independent distribution channel and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time.

What is the trip class of this motor protection circuit breaker?

It is Trip Class 10, meaning it will trip within 10 seconds at a 7.2x overload setting, suitable for standard induction motor starting.

Does the 3RV2041-4HA15 mount on a standard DIN rail?

Yes, it mounts via screw and snap-on onto 35 mm DIN rail per DIN EN 60715, in any mounting position.

MPN
3RV2041-4HA15