For a panel with a transformer-fed 400 V bus, this breaker coordinates with upstream fuses or a molded-case breaker sized above 65 kA.
Terminals and wiring
Screw-type terminals on the main circuit accept 2x (2.5 to 50 mm²) solid or stranded, or 1x (10 to 70 mm²). That covers most motor feeds up to about 95 A — the rated current at 480 V and 600 V is 93 A. Auxiliary and control wiring uses the smaller terminal range: 2x (2.5 to 16 mm²). The 176 mm depth and 70 mm width leave clearance for adjacent breakers; side clearance is 30 mm, top and bottom 150 mm each for arc venting and heat dissipation.