Skip to main content
Siemens 3RV2042-4MB10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2042-4MB10 SIRIUS Motor Protection Circuit Breake

MPN3RV2042-4MB10
Active

Siemens SIRIUS, motor protection circuit breaker, 3RV2042-4MB10, CLASS 20, screw-type terminals, 100 kA breaking capacity at 400 V AC, for 35 mm DIN rail.

$232.41Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RV2042-4MB10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS3
3RV2042-4MB10 — Electrical
ParameterValue
Rated operational current (Ie)100 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 31 000 V
Rated impulse withstand voltage (Uimp)8 kV
Number of poles3
Power loss (AC, hot)44 W
Power loss, per pole (AC, hot)14.7 W
3RV2042-4MB10 — Protection & Tripping
ParameterValue
Overload release setting range80 ... 100 A
Instantaneous short-circuit trip current1 300 A
Trip classCLASS 20
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)10 kA
Breaking capacity at 690 V (AC)6 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V3 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2042-4MB10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)25 000
Endurance, auxiliary contacts (typ.)25 000
Switching frequency, AC-3 (max.)15 1/h
3RV2042-4MB10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (2,5 ... 50 mm²), 1x (10 ... 70 mm²)
Conductor cross-section, finely stranded with ferrule2x (2.5 ... 35 mm²), 1x (2.5 ... 50 mm²)
3RV2042-4MB10 — Mechanical
ParameterValue
Height165 mm
Width70 mm
Depth176 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2042-4MB10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2042-4MB10 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

The Siemens SIRIUS 3RV2042-4MB10 is a motor protection circuit breaker designed for the main current circuit, with a CLASS 20 trip characteristic that allows it to ride through motor inrush without nuisance tripping — the right curve for standard induction motors driving pumps, fans, and compressors. Phase failure detection is built in, so it catches a lost phase before the motor cooks. Breaking capacity is 100 kA at 400 V AC — that's the interrupting rating at the panel's line side, meaning it can clear a bolted fault at that level without upstream breakers needing to back it up. At 690 V AC the rating drops to 6 kA, so verify the available fault current at the installation point. Mounts on 35 mm DIN rail per DIN EN 60715, with screw and snap-on fastening. Dimensions are 70 mm wide, 165 mm high, 176 mm deep — fits standard motor control center buckets. Screw-type terminals on the main circuit accept 2x (2.5 to 16 mm²) solid or stranded, or up to 70 mm² on a single conductor.

Deployment Context

Snap-on mounting onto 35 mm DIN rail means it integrates directly into a standard motor control center or panel enclosure — no adapter plate needed. The any-position mounting orientation gives flexibility in tight layouts. Operating temperature range of -20 to +60 °C covers most indoor industrial environments; storage range extends to -50 to +80 °C, which matters for cold-chain or unheated warehouse staging before commissioning.

Frequently asked questions

Where can I buy 3RV2042-4MB10 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time, not listed here.

What is the breaking capacity of 3RV2042-4MB10 at 400 V?

100 kA at 400 V AC — sufficient for high-fault-capacity industrial panels without upstream series rating coordination.

Does 3RV2042-4MB10 detect phase failure?

Yes, phase failure detection is built in, protecting the motor from single-phasing damage.

What trip class is 3RV2042-4MB10?

CLASS 20, meaning it allows up to 20 seconds of overload at 600% of the thermal setting — standard for general-purpose induction motor starting.

MPN
3RV2042-4MB10