SCCR and breaking capacity
At 240 V AC it's also 100 kA. The SCCR covers the full range from 20 V to 690 V, meaning this breaker can be used on 208 V, 240 V, 400 V, 480 V, and 690 V systems without derating the interrupting rating.
Dimensions: 65 mm wide, 97 mm deep, 97 mm tall.
Terminals and wiring
Screw-type terminals on the main current circuit, accepting 2× (0.5 to 1.5 mm²) or 2× (0.75 to 2.5 mm²) solid or stranded copper. Screwdriver shaft diameter 5 to 6 mm.