Skip to main content
Siemens 3RV2111-0HA10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2111-0HA10 SIRIUS Motor Circuit Breaker, 100 kA a

MPN3RV2111-0HA10
Active

Siemens SIRIUS motor-protective circuit breaker, 3RV2111-0HA10, 100 kA breaking capacity at 400 V AC, Class 10 trip, screw and snap-on mounting for 35 mm DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RV2111-0HA10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV2111-0HA10 — Electrical
ParameterValue
Rated operational current (Ie)0.8 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W
3RV2111-0HA10 — Protection & Tripping
ParameterValue
Overload release setting range0.55 ... 0.8 A
Instantaneous short-circuit trip current10 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V100 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2111-0HA10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0
3RV2111-0HA10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (18 ... 14), 2x 12
3RV2111-0HA10 — Mechanical
ParameterValue
Height97 mm
Width65 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
Mounting positionany
3RV2111-0HA10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2111-0HA10 — Specifications
ParameterValue
Design Of The ProductFor motor protection with overload relay function

Product details

The Siemens 3RV2111-0HA10 is a SIRIUS motor-protective circuit breaker with integrated overload relay function — designed to protect motor feeders against short-circuit and overload in a single device. It carries a 100 kA breaking capacity at 400 V AC, also rated 100 kA at 500 V and 690 V.

Ground fault detection is not included; if that's required, you'd need an upstream RCD or a separate ground-fault module. The rated switching frequency at AC-3 duty is 15 operations per hour — fine for a pump or fan cycling a few times an hour, not for a rapid-reversing application.

Mounting position is any. The device footprint is 65 mm wide × 97 mm high × 97 mm deep — a standard two-module width on the DIN rail. Clearance requirements: 50 mm upwards and downwards, 30 mm at the sides; forwards and backwards clearance is 0 mm, so it can sit flush against the back panel. Main contact terminals are M3 screw-type, accepting 2× (0.5…1.5 mm²) or 2× (0.75…2.5 mm²) solid or stranded wire.

Frequently asked questions

How do I get current pricing and availability for 3RV2111-0HA10?

Sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time.

What is 3RV2111-0HA10's listed depth?

The depth is 97 mm. Overall dimensions are 65 mm wide × 97 mm high × 97 mm deep.

Will 3RV2111-0HA10 drop into a panel specified around 3RV2011-0AA10 without rewiring?

Both are SIRIUS motor-protective circuit breakers with the same 65 mm width and snap-on DIN-rail mounting, so the footprint and rail position are compatible. Terminal type and wire range may differ — verify the 3RV2011-0AA10's terminal specs against the 3RV2111-0HA10's M3 screw terminals accepting 2×(0.5…1.5 mm²) or 2×(0.75…2.5 mm²) before assuming a direct swap.

MPN
3RV2111-0HA10