Rated operating voltage spans 20 to 690 V, and the interrupting capacity holds at 100 kA at 240 V, 400 V, 500 V, and 690 V — that is full-rated SCCR across the common industrial voltages without derating.
Mounting position is any orientation. Clearance: 50 mm upward, 50 mm downward, 30 mm at the side; zero forward or backward clearance required. Dimensions: 97 mm depth, 65 mm width, 97 mm height. Main circuit terminals accept screw-type connections, 2× (0.5 to 1.5 mm²) solid or stranded, or 2× (0.75 to 2.5 mm²). Main contact screws are M3.
Motor protection features and limits
Ground fault detection is not included; that requires a separate module. Maximum switching frequency under AC-3 (motor) duty is 15 operations per hour; same under AC-3e. That limits the part to infrequent starts — not suitable for jogging or rapid cycling. Auxiliary contact ratings: 1 A at 24 V, 1.5 A at 230 V. For fuse backup, the maximum gL/gG fuse is 20 A at 500 V, 16 A at 690 V.