Skip to main content
Siemens 3RV2111-1DA10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2111-1DA10 SIRIUS Motor Protection Circuit Breake

MPN3RV2111-1DA10
Active

Siemens SIRIUS motor protection circuit breaker, 3RV2111-1DA10, Class 10, screw and snap-on DIN rail mounting, 100 kA breaking capacity at 400 V.

$54.61Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RV2111-1DA10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV2111-1DA10 — Electrical
ParameterValue
Rated operational current (Ie)3.2 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W
3RV2111-1DA10 — Protection & Tripping
ParameterValue
Overload release setting range2.2 ... 3.2 A
Instantaneous short-circuit trip current42 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)10 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V10 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2111-1DA10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0
3RV2111-1DA10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (18 ... 14), 2x 12
3RV2111-1DA10 — Mechanical
ParameterValue
Height97 mm
Width65 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
Mounting positionany
3RV2111-1DA10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2111-1DA10 — Specifications
ParameterValue
Design Of The ProductFor motor protection with overload relay function

Product details

Any mounting position is allowed. That's another SKU I don't need to worry about for panel layout — just keep the 50 mm vertical breathing room.

Compared to the 3RV2021-1FA15, this 3RV2111-1DA10 shares the same SIRIUS family and Class 10 trip, but the 3RV2021-1FA15 is a higher-current variant with a different adjustment range. The 3RV2111-1DA10 is the lower-current sibling — check the actual setting range on the nameplate to confirm fit for your motor FLA.

Breaking capacity: 100 kA at 240 V, 400 V, and 500 V; 10 kA at 690 V. Terminal screws for main contacts are M3, accepting 2×(0.5…1.5 mm²) or 2×(0.75…2.5 mm²) solid or stranded copper.

Frequently asked questions

Where can I buy 3RV2111-1DA10 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

When sourcing 3RV2111-1DA10, what's the closest functional second-source — 3RV2021-1FA15?

The 3RV2021-1FA15 is a higher-current sibling in the same SIRIUS family with the same Class 10 trip and DIN-rail mounting. It will drop into the same panel footprint without rewiring, but verify the adjustment range matches your motor FLA.

What is 3RV2111-1DA10's listed depth (97 mm) on this component line?

The depth is 97 mm, width 65 mm, height 97 mm.

Will 3RV2111-1DA10 drop into a panel that was specified around 3RV2021-1FA15 without rewiring?

Yes — both use the same screw/snap-on DIN rail mounting and similar clearance envelopes, so a panel laid out for the 3RV2021-1FA15 will accept the 3RV2111-1DA10 without rewiring the rail.

What compliance documentation does this brand provide for 3RV2111-1DA10 (RoHS, REACH, UL, IEC)?

Standard SIRIUS motor protection circuit breaker approvals apply. RoHS, REACH, UL, and IEC documentation is available from the manufacturer upon request.

MPN
3RV2111-1DA10