Motor protection circuit breaker with integrated overload relay
Rated at 65 A (at 480 V) and 62 A (at 600 V), this breaker handles motor loads up to 18.5 kW at 230 V or 25 hp at 220/230 V. The breaking capacity reaches 30 kA at 400 V, 5 kA at 500 V, and 2 kA at 690 V — sufficient for most industrial distribution panels with transformer-fed fault currents. Any mounting position is allowed. Screw-type terminals accept 2× (1…35 mm²) or 1× (1…50 mm²) solid or stranded copper, with M6 main contact bolts.
Dimensions: 75 mm wide, 140 mm high, 149 mm deep — fits standard 8-module-wide DIN-rail spacing. Switching frequency limited to 15 operations per hour at AC-3 and AC-3e duty — adequate for motor starting cycles in conveyor, pump, and fan applications. For higher cycling (frequent jogging or inching), consider a contactor-based solution with a separate motor protection relay.