Skip to main content
Siemens 3RV2131-4JA10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2131-4JA10 SIRIUS Motor Protection Circuit Breake

MPN3RV2131-4JA10
Active

Siemens SIRIUS 3RV2131-4JA10 motor protection circuit breaker with integrated overload relay function, 65 A rated current, 30 kA breaking capacity at 400 V AC, Trip Class 10, screw terminals, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RV2131-4JA10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS2
3RV2131-4JA10 — Electrical
ParameterValue
Rated operational current (Ie)65 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)26 W
Power loss, per pole (AC, hot)8.7 W
3RV2131-4JA10 — Protection & Tripping
ParameterValue
Overload release setting range54 ... 65 A
Instantaneous short-circuit trip current845 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)65 kA
Breaking capacity at 400 V (AC)65 kA
Breaking capacity at 500 V (AC)8 kA
Breaking capacity at 690 V (AC)4 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V2 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2131-4JA10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)20 000
Endurance, auxiliary contacts (typ.)20 000
Switching frequency, AC-3 (max.)15 1/h
3RV2131-4JA10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (1 ... 35 mm²), 1x (1 ... 50 mm²)
Conductor cross-section, finely stranded with ferrule2x (1 ... 25 mm²), 1x (1 ... 35 mm²)
3RV2131-4JA10 — Mechanical
ParameterValue
Height140 mm
Width75 mm
Depth149 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2131-4JA10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2131-4JA10 — Specifications
ParameterValue
Design Of The ProductFor motor protection with overload relay function

Product details

Motor protection circuit breaker with integrated overload relay

Rated at 65 A (at 480 V) and 62 A (at 600 V), this breaker handles motor loads up to 18.5 kW at 230 V or 25 hp at 220/230 V. The breaking capacity reaches 30 kA at 400 V, 5 kA at 500 V, and 2 kA at 690 V — sufficient for most industrial distribution panels with transformer-fed fault currents. Any mounting position is allowed. Screw-type terminals accept 2× (1…35 mm²) or 1× (1…50 mm²) solid or stranded copper, with M6 main contact bolts.

Dimensions: 75 mm wide, 140 mm high, 149 mm deep — fits standard 8-module-wide DIN-rail spacing. Switching frequency limited to 15 operations per hour at AC-3 and AC-3e duty — adequate for motor starting cycles in conveyor, pump, and fan applications. For higher cycling (frequent jogging or inching), consider a contactor-based solution with a separate motor protection relay.

Frequently asked questions

What is the breaking capacity of the 3RV2131-4JA10 at 400 V?

The 3RV2131-4JA10 has a breaking capacity of 30 kA at 400 V AC, 5 kA at 500 V, and 2 kA at 690 V. At 240 V it reaches 100 kA.

Does the 3RV2131-4JA10 include phase failure protection?

Yes, phase failure detection is built into the 3RV2131-4JA10. It will trip the circuit if a phase is lost, preventing single-phasing damage to the motor.

What wire sizes fit the 3RV2131-4JA10 terminals?

The screw-type main circuit terminals accept 2× (1…35 mm²) or 1× (1…50 mm²) solid or stranded copper conductors. Main contact bolts are M6.

How do I get current pricing and availability for the 3RV2131-4JA10?

Submit an RFQ through this listing. Pricing and availability are confirmed at quote time through independent distribution channels — no stock count or price is published here.

What is the closest functional second-source for the 3RV2131-4JA10?

The 3RV2023-4DA10 is a similar SIRIUS motor protection circuit breaker but in a smaller frame size with lower ratings. It will not drop into a panel wired for the 3RV2131-4JA10 without rewiring — the terminal spacing, width, and clearance distances differ. Verify your load current and fault current requirements before substituting.