Skip to main content
Siemens 3RV2131-4WA10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2131-4WA10 SIRIUS Motor Protection Circuit Breake

MPN3RV2131-4WA10
Active

Siemens SIRIUS motor protection circuit breaker with integrated overload relay function, order code 3RV2131-4WA10, Class 10 trip, 30 kA breaking capacity at 400 V, screw-type terminals, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV2131-4WA10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS2
3RV2131-4WA10 — Electrical
ParameterValue
Rated operational current (Ie)52 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)24.5 W
Power loss, per pole (AC, hot)8.2 W
3RV2131-4WA10 — Protection & Tripping
ParameterValue
Overload release setting range42 ... 52 A
Instantaneous short-circuit trip current741 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)65 kA
Breaking capacity at 500 V (AC)8 kA
Breaking capacity at 690 V (AC)4 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V2 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2131-4WA10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)50 000
Endurance, auxiliary contacts (typ.)50 000
Switching frequency, AC-3 (max.)15 1/h
3RV2131-4WA10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (1 ... 35 mm²), 1x (1 ... 50 mm²)
Conductor cross-section, finely stranded with ferrule2x (1 ... 25 mm²), 1x (1 ... 35 mm²)
Conductor range, AWG (main contacts)2x (18 ... 2), 1x (18 ... 1)
3RV2131-4WA10 — Mechanical
ParameterValue
Height140 mm
Width75 mm
Depth149 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2131-4WA10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2131-4WA10 — Specifications
ParameterValue
Design Of The ProductFor motor protection with overload relay function

Product details

Terminal capacity accepts up to 2x 35 mm² or 1x 50 mm² solid/stranded copper, using M6 screw-type terminals on the main circuit. No ground fault detection on this variant.

Breaking capacity across voltage levels

The interrupting capacity varies by line voltage: 100 kA at 240 V, 30 kA at 400 V, 4 kA at 500 V, and 2 kA at 690 V. For 480 V systems it's rated 52 A continuous, and at 600 V also 52 A continuous. Maximum switching frequency under AC-3 duty (motor starting) is 15 operations per hour — fine for conveyor or pump cycling, but not for rapid reversing applications.

Dimensions and clearances

Physical footprint: 75 mm wide, 140 mm tall, 149 mm deep. Required clearances for heat dissipation: 50 mm above and below, 10 mm to the side, zero forward or backward clearance needed.

Frequently asked questions

Where can I buy 3RV2131-4WA10 and get a price?

This part is sourced through independent distribution channels and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

What is the breaking capacity of 3RV2131-4WA10 at 400 V?

30 kA at 400 V, with higher interrupting ratings at lower voltages (100 kA at 240 V) and derated at higher voltages (2 kA at 690 V).

Does 3RV2131-4WA10 include phase failure protection?

Yes, phase failure detection is built in — the breaker trips if one phase drops, protecting the motor from single-phasing damage.

What trip class is the 3RV2131-4WA10?

Class 10, meaning it clears overloads within 10 seconds at 7.2x the current setting — suitable for standard induction motor protection during start-up.

MPN
3RV2131-4WA10