Skip to main content
Siemens 3RV2142-4JA10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2142-4JA10 SIRIUS Motor Protection Circuit Breake

MPN3RV2142-4JA10
Active

Siemens SIRIUS motor protection circuit breaker, 3RV2142-4JA10, with overload relay function, Trip Class 10, 50 kA at 400 V, screw-type terminals, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RV2142-4JA10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS3
3RV2142-4JA10 — Electrical
ParameterValue
Rated operational current (Ie)63 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 31 000 V
Rated impulse withstand voltage (Uimp)8 kV
Number of poles3
Power loss (AC, hot)34 W
Power loss, per pole (AC, hot)11.3 W
3RV2142-4JA10 — Protection & Tripping
ParameterValue
Overload release setting range45 ... 63 A
Instantaneous short-circuit trip current819 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)15 kA
Breaking capacity at 690 V (AC)7.5 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V4 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2142-4JA10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)25 000
Endurance, auxiliary contacts (typ.)25 000
Switching frequency, AC-3 (max.)15 1/h
3RV2142-4JA10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (2,5 ... 50 mm²), 1x (10 ... 70 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
3RV2142-4JA10 — Mechanical
ParameterValue
Height165 mm
Width90 mm
Depth176 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2142-4JA10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2142-4JA10 — Specifications
ParameterValue
Design Of The ProductFor motor protection with overload relay function

Product details

What it is and where it fits

The Siemens 3RV2142-4JA10 is a SIRIUS motor protection circuit breaker with an integrated overload relay function, designed to protect motors against short circuits, overloads, and phase failure. It snaps onto 35 mm DIN rail per DIN EN 60715 and uses screw-type terminals for the main circuit, so it lands in a standard motor control center or panel without surprises. Rated breaking capacity hits 50 kA at 400 V, which is enough to handle a stiff utility fault without cascading upstream. The Trip Class 10 means it trips fast enough to protect standard induction motors during a locked-rotor event — out here in the grease, that's the difference between a quick restart and a rewind job.

Key ratings and what they mean for your panel

At 400 V, the 50 kA interrupting rating covers most industrial secondary-side faults. At 690 V, it still holds 4 kA — enough for a 690 V motor branch in a European-style panel. The unit also carries a 63 A continuous rating at 480 V and 600 V, so it sizes into the 40–60 A motor range comfortably. Phase failure detection is built in — the unit will drop the motor on a lost phase before single-phasing cooks the winding. No ground fault detection on this variant, so if you need that, you'd add a separate ground-fault module downstream. Mounting position is any, which helps when you're squeezing this into a tight corner of the enclosure. Clearance requirements: 150 mm above and below, 30 mm to the side, and zero forward or backward — so it can sit flush against the backplane.

Lifecycle and sourcing reality

Sourcing is straightforward — we quote this part to order against an RFQ through our independent distribution channels. Availability and current pricing are confirmed at quote time. No long lead-time surprises on an active-line item like this.

Frequently asked questions

What is the breaking capacity of 3RV2142-4JA10 at 400 V?

The rated breaking capacity at 400 V is 50 kA. At 690 V it drops to 4 kA.

What is the trip class of this motor protection circuit breaker?

It is Trip Class 10, which means it will trip within 10 seconds at a locked-rotor current of 7.2× the thermal setting — standard protection for most general-purpose motors.

Where can I buy 3RV2142-4JA10 and what is the price?

This part is sourced to order against an RFQ through our independent distribution network. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

MPN
3RV2142-4JA10