It is rated for a continuous current of 84 A at 400 V and 480/600 V, with a breaking capacity of 50 kA at 400 V AC — sufficient for most industrial distribution panels.
Dimensions are 90 mm wide, 165 mm high, 176 mm deep — a standard three-module-wide footprint on the rail. The screw-type terminals on the main circuit accept 2× (2.5–16 mm²) solid or 2× (2.5–50 mm²) stranded, with a single conductor up to 70 mm² stranded.
Breaking capacity and voltage ratings
Breaking capacity varies by voltage: 100 kA at 240 V, 50 kA at 400 V, 5 kA at 500 V, and 3 kA at 690 V. The 84 A rated current holds at both 480 V and 600 V. Motor horsepower ratings are provided for common North American voltages: 15 hp at 230 V, 30 hp at 220/230 V, 60 hp at 460/480 V, and 75 hp at 575/600 V.
No end-of-life notification or successor part is recorded.
Environmental limits
Mounting position is any orientation. Maximum switching frequency at AC-3 and AC-3e duty is 15 operations per hour.