SIRIUS S00 circuit breaker for starter combinations
The 100 kA breaking capacity at 400 V AC (and at 240, 500, 690 V AC) means it can safely interrupt fault currents up to that level without cascading upstream, which is the figure that governs SCCR for the panel.
Any mounting position is permitted. Clearance: 50 mm above and below, 30 mm at the sides; zero forward or backward clearance needed, so it can sit tight against the back panel or enclosure wall.