The 100 kA interrupting rating holds at 240 V, 400 V, 500 V, and 690 V AC — that's a flat high-fault curve, not a derating as voltage climbs. At 480 V and 600 V the motor full-load current ratings are 1.6 A, so this size S0 frame is suited for smaller motor branches (0.1 hp at 230 V, 1 hp at 460/480 V, 0.8 hp at 575/600 V) where the fault current at the panel might still be high.
Any mounting position is acceptable, which simplifies layout in tight enclosures.