Skip to main content
Siemens 3RV2332-4EC10 — Motor Protection Circuit Breakers (MPCB)

Siemens SIRIUS 3RV2332-4EC10 Circuit Breaker, 32 A, 50 kA at

MPN3RV2332-4EC10
Active

Siemens SIRIUS circuit breaker, type 3RV2332-4EC10, for starter combinations, 32 A rated at 480/600 V, 50 kA breaking capacity at 400 V, screw terminals, snap-on 35 mm DIN rail.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV2332-4EC10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS2

Electrical

3RV2332-4EC10 — Electrical
ParameterValue
Rated operational current (Ie)32 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)18 W
Power loss, per pole (AC, hot)6 W

Protection & Tripping

3RV2332-4EC10 — Protection & Tripping
ParameterValue
Instantaneous short-circuit trip current416 A
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)15 kA
Breaking capacity at 690 V (AC)6 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V4 kA
Short-circuit trip typemagnetic
Short-circuit protectionYes
Phase-failure detectionNo
Ground-fault detectionNo
Auxiliary switch extendableYes

Endurance & Switching

3RV2332-4EC10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)50 000
Endurance, auxiliary contacts (typ.)50 000
Switching frequency, AC-3 (max.)15 1/h

Connections

3RV2332-4EC10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (1 ... 35 mm²), 1x (1 ... 50 mm²)
Conductor cross-section, finely stranded with ferrule2x (1 ... 25 mm²), 1x (1 ... 35 mm²)
Conductor range, AWG (main contacts)2x (18 ... 2), 1x (18 ... 1)

Mechanical

3RV2332-4EC10 — Mechanical
ParameterValue
Height140 mm
Width55 mm
Depth149 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
Mounting positionany

Environmental

3RV2332-4EC10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m

Specifications

3RV2332-4EC10 — Specifications
ParameterValue
Design Of The ProductFor starter combinations

Product details

Siemens SIRIUS 3RV2332-4EC10 is a circuit breaker designed specifically for starter combinations — meaning it integrates into a motor starter assembly with a contactor and overload relay, not as a standalone feeder breaker. Rated 32 A at 480 V and 32 A at 600 V, with a breaking capacity of 50 kA at 400 V and 100 kA at 240 V. That 50 kA at 400 V tells you it can handle high-fault-current industrial panels without cascading upstream — the SCCR headroom is there for the line side. It uses screw-type terminals on the main circuit, accepting up to 2x 35 mm² or 1x 50 mm² solid or stranded copper.

Mounting and integration

Snap-on mounting onto a 35 mm standard mounting rail per DIN EN 60715, with screw fastening for security. Mounting position any orientation — no derating for side or upside-down mounting. Clearance: 50 mm upward and downward, 10 mm to the side, zero forward or backward. That zero forward clearance means it can sit flush against a back panel or enclosure wall — handy when packing multiple breakers in a shallow gland plate layout. Dimensions: 55 mm wide, 140 mm high, 149 mm deep.

Electrical ratings and environment

Rated voltage range 20 to 690 V AC. Breaking capacity varies by voltage: 100 kA at 240 V, 50 kA at 400 V, 8 kA at 500 V, 4 kA at 690 V. That drop-off at 690 V is typical for a 32 A frame — the arc extinction limits the high-voltage interruption. Operating temperature -20 to +60 °C, storage -50 to +80 °C. No ground-fault or phase-failure detection built in — this is a thermal-magnetic or electronic motor-protective breaker, not a full power monitor. Main contact terminals are M6 bolts.

Frequently asked questions

How do I get current pricing and availability for 3RV2332-4EC10?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through our independent distribution network.

Will 3RV2332-4EC10 drop into a panel specified around 3RV2023-4DA10 without rewiring?

Both are Siemens SIRIUS circuit breakers on the same 35 mm DIN rail footprint, so the mechanical fit is the same. But the 3RV2332-4EC10 is rated 32 A at 480/600 V versus the lower frame of the 3RV2023 series — verify the load current and breaking capacity requirements before swapping, as the upstream protection coordination may differ.

What compliance documentation does Siemens provide for 3RV2332-4EC10?

Siemens SIRIUS products typically carry UL, CSA, CE, and IEC certifications. Specific documentation (RoHS, REACH, declaration of conformity) is available on request with the order.

MPN