The 3RV2341-4MC10 occupies 70 mm width, 165 mm height, and 176 mm depth on the DIN rail. The main circuit uses screw-type terminals accepting 2x (2.5...16 mm²) solid or 2x (2.5...50 mm²) / 1x (10...70 mm²) stranded. Wire the line and load through these; the auxiliary terminals are separate. Motor horsepower ratings span 7.5 hp at 110/120 V up to 100 hp at 575/600 V, covering a wide range of induction motor sizes.
Environmental and mounting notes
The part has no ground fault or phase failure detection — it is a straight thermal-magnetic or electronic overload device for motor protection, not a multifunction monitor. Rated switching frequency for AC-3 and AC-3e duty is 15 operations per hour maximum, so it is intended for intermittent motor starting, not continuous switching.