Siemens 3RV2341-4MC10 SIRIUS Circuit Breaker, 400 V 65 kA

MPN3RV2341-4MC10
Active

Siemens SIRIUS circuit breaker for starter combinations, 3RV2341-4MC10, 400 V 65 kA, screw terminals, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV2341-4MC10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS3
3RV2341-4MC10 — Electrical
ParameterValue
Rated operational current (Ie)100 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 31 000 V
Rated impulse withstand voltage (Uimp)8 kV
Number of poles3
Power loss (AC, hot)44 W
Power loss, per pole (AC, hot)14.7 W
3RV2341-4MC10 — Protection & Tripping
ParameterValue
Instantaneous short-circuit trip current1 300 A
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)65 kA
Breaking capacity at 500 V (AC)8 kA
Breaking capacity at 690 V (AC)5 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V3 kA
Short-circuit trip typemagnetic
Short-circuit protectionYes
Phase-failure detectionNo
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2341-4MC10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)25 000
Endurance, auxiliary contacts (typ.)25 000
Switching frequency, AC-3 (max.)15 1/h
3RV2341-4MC10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (2,5 ... 50 mm²), 1x (10 ... 70 mm²)
Conductor cross-section, finely stranded with ferrule2x (2.5 ... 35 mm²), 1x (2.5 ... 50 mm²)
3RV2341-4MC10 — Mechanical
ParameterValue
Height165 mm
Width70 mm
Depth176 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2341-4MC10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2341-4MC10 — Specifications
ParameterValue
Design Of The ProductFor starter combinations

Product details

The 3RV2341-4MC10 occupies 70 mm width, 165 mm height, and 176 mm depth on the DIN rail. The main circuit uses screw-type terminals accepting 2x (2.5...16 mm²) solid or 2x (2.5...50 mm²) / 1x (10...70 mm²) stranded. Wire the line and load through these; the auxiliary terminals are separate. Motor horsepower ratings span 7.5 hp at 110/120 V up to 100 hp at 575/600 V, covering a wide range of induction motor sizes.

Environmental and mounting notes

The part has no ground fault or phase failure detection — it is a straight thermal-magnetic or electronic overload device for motor protection, not a multifunction monitor. Rated switching frequency for AC-3 and AC-3e duty is 15 operations per hour maximum, so it is intended for intermittent motor starting, not continuous switching.

Frequently asked questions

How do I get current pricing and availability for 3RV2341-4MC10?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is 3RV2341-4MC10's listed depth?

The depth is 176 mm.

What wire sizes does the 3RV2341-4MC10 accept?

Solid wire: 2x (2.5...16 mm²). Stranded: 2x (2.5...50 mm²) or 1x (10...70 mm²).

Will 3RV2341-4MC10 drop into a panel specified around 3RV2021-4NA25 without rewiring?

Both are SIRIUS circuit breakers for starter combinations on 35 mm DIN rail, but the 3RV2341-4MC10 is a physically larger frame (70 mm wide vs the 3RV2021 series typically 45 mm). Check the panel depth and clearance — the 3RV2341-4MC10 requires 150 mm above and below, and its 176 mm depth may exceed the earlier frame's footprint. Terminals are screw-type on both, but wire range differs; verify the lug sizes against your existing wiring.

MPN