Skip to main content
Siemens 3RV2411-0AA10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2411-0AA10 SIRIUS Circuit Breaker, Transformer Pr

MPN3RV2411-0AA10
Active

Siemens SIRIUS 3RV2411-0AA10 circuit breaker, size S00, for transformer protection, Class 10 trip, 100 kA breaking capacity at 400 V AC, phase failure detection, screw and snap-on 35 mm DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV2411-0AA10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV2411-0AA10 — Electrical
ParameterValue
Rated operational current (Ie)0.16 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W
3RV2411-0AA10 — Protection & Tripping
ParameterValue
Overload release setting range0.11 ... 0.16 A
Instantaneous short-circuit trip current3.3 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V100 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2411-0AA10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0
3RV2411-0AA10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0,75 ... 2,5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (18 ... 14), 2x 12
3RV2411-0AA10 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2411-0AA10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2411-0AA10 — Specifications
ParameterValue
Design Of The ProductFor transformer protection

Product details

Transformer-protection circuit breaker, SIRIUS 3RV2411-0AA10

Rated breaking capacity hits 100 kA at 400 V AC and holds that figure at 240 V, 500 V, and 690 V AC. That's a high-interrupting rating for a size S00 frame — it clears a bolted fault upstream of the transformer without cascading to the main breaker. No ground-fault detection on this variant — that's a separate add-on module when needed.

Screw-type terminals on the main circuit accept 2x 0.75–2.5 mm² solid/stranded or 2x 4 mm². That's typical for S00 breakers — leaves room for cable bending and heat dissipation.

Frequently asked questions

Will 3RV2411-0AA10 drop into a panel specified for 3RV2011-0AA10?

Yes, both are size S00 with the same 45 mm width and 97 mm depth, and both mount on 35 mm DIN rail per DIN EN 60715. The terminal specifications are identical, so no rewiring or panel modification is needed.

MPN
3RV2411-0AA10