Skip to main content
Siemens 3RV2411-0AA20 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2411-0AA20 SIRIUS Circuit Breaker, 100 kA at 400

MPN3RV2411-0AA20
Active

Siemens SIRIUS circuit breaker, 3RV2411-0AA20, Size S00, for transformer protection, Trip Class 10, 100 kA breaking capacity at 400 V AC, screw and snap-on DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV2411-0AA20 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV2411-0AA20 — Electrical
ParameterValue
Rated operational current (Ie)0.16 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W
3RV2411-0AA20 — Protection & Tripping
ParameterValue
Overload release setting range0.11 ... 0.16 A
Instantaneous short-circuit trip current3.3 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V100 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2411-0AA20 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0
3RV2411-0AA20 — Connections
ParameterValue
Main-circuit terminal typespring-loaded terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0,5 ... 4 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (20 ... 12)
3RV2411-0AA20 — Mechanical
ParameterValue
Height106 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
Mounting positionany
3RV2411-0AA20 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2411-0AA20 — Specifications
ParameterValue
Design Of The ProductFor transformer protection

Product details

It mounts on a 35 mm DIN rail per DIN EN 60715 using either screws or the integrated snap-on clip, and the Size S00 frame keeps the footprint compact at 45 mm wide by 97 mm deep.

No ground fault detection on this variant, so if that's required, you'd need a separate GFCI or a different order code.

Mounting position is any, so vertical or horizontal panel layouts work. Clearance: 50 mm above and below, 30 mm to the side, zero forward or backward — that's tight enough for dense DIN-rail packing but leaves room for wiring fingers. Use a 3 mm diameter screwdriver with a 3.0 × 0.5 mm tip for the terminal screws.

Frequently asked questions

Where can I buy 3RV2411-0AA20 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is 3RV2411-0AA20's listed depth?

The depth is 97 mm, with a width of 45 mm and height of 106 mm.

Will 3RV2411-0AA20 drop into a panel specified around 3RV1011-0GA10 without rewiring?

Both are Size S00 circuit breakers on the same 35 mm DIN rail footprint, so the mechanical fit and rail mounting are identical. However, 3RV2411-0AA20 is designed for transformer protection with a different trip curve and breaking capacity than the 3RV1011-0GA10; verify the protection coordination and terminal wiring before swapping.

What compliance documentation does Siemens provide for 3RV2411-0AA20?

As a standard Siemens SIRIUS industrial control product, this circuit breaker is designed to meet applicable IEC and UL standards for circuit breakers. Specific compliance certificates (RoHS, REACH, UL, IEC) are available in the Siemens Industry Online Support documentation package for this order code.

MPN
3RV2411-0AA20