Skip to main content
Siemens 3RV2411-0KA10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2411-0KA10 SIRIUS Circuit Breaker, 100 kA, Class

MPN3RV2411-0KA10
Active

Siemens SIRIUS 3RV2411-0KA10, circuit breaker for transformer protection, 45 mm width, 97 mm depth, 100 kA breaking capacity at 400 V AC, Trip Class 10, screw and snap-on DIN rail mounting.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV2411-0KA10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV2411-0KA10 — Electrical
ParameterValue
Rated operational current (Ie)1.25 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W
3RV2411-0KA10 — Protection & Tripping
ParameterValue
Overload release setting range0.9 ... 1.25 A
Instantaneous short-circuit trip current26 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V100 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2411-0KA10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0
3RV2411-0KA10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0,75 ... 2,5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (18 ... 14), 2x 12
3RV2411-0KA10 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2411-0KA10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2411-0KA10 — Specifications
ParameterValue
Design Of The ProductFor transformer protection

Product details

Transformer-protection circuit breaker with 100 kA interrupting capacity

The Siemens SIRUS 3RV2411-0KA10 is a circuit breaker designed specifically for transformer protection, not general motor or feeder duty. The 45 mm width and 97 mm depth fit a standard 35 mm DIN rail (DIN EN 60715) with screw and snap-on fastening, so it drops into existing SIRIUS 3RV mounting rails without panel rework.

Mounting and clearance — panel fit

Mounting position is any, so vertical or horizontal orientation in the enclosure is fine. Clearance requirements: 50 mm upward, 50 mm downward, 30 mm at the side. Zero forward clearance needed, which helps when the panel door or a busbar shroud is close. The screw-type terminals on the main current circuit accept 2×(0.75–2.5 mm²) solid/stranded or 2×4 mm² — M3 screws for the main contacts. For a transformer-protection install, the 0.2 kW rating at 230 V and 1 hp at 460/480 V give a quick horsepower-to-kW cross-check for the protected transformer's secondary.

The lifecycle stage is listed as current, meaning Siemens continues to manufacture the 3RV2411-0KA10 as an active catalog line. No last-time-buy or phase-out notice is on record.

MPN
3RV2411-0KA10