Specifications

3RV2411-1DA15 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV2411-1DA15 — Electrical
ParameterValue
Rated operational current (Ie)3.2 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W
3RV2411-1DA15 — Protection & Tripping
ParameterValue
Overload release setting range2.2 ... 3.2 A
Instantaneous short-circuit trip current65 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)10 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V10 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2411-1DA15 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0
3RV2411-1DA15 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (18 ... 14), 2x 12
3RV2411-1DA15 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2411-1DA15 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2411-1DA15 — Specifications
ParameterValue
Design Of The ProductFor transformer protection

Product details

The Siemens 3RV2411-1DA15 is a SIRIUS circuit breaker specifically designed for transformer protection. The 97 mm height is consistent with the SIRIUS 3RV2 compact form factor, so it aligns vertically with contactors and overload relays in a standard motor control center layout.

Breaking capacity is 100 kA at 400 V and 500 V, dropping to 10 kA at 690 V. On a three-phase transformer bank, if one primary fuse blows the breaker will trip on the secondary side, preventing single-phasing the load. No separate phase-loss relay needed. The auxiliary contact ratings cover 1 A at 24 V and 0.5 A at 230 V — enough to drive a PLC input or a small relay for remote trip indication. The main contact terminals accept 2× (0.5 to 1.5 mm²) or 2× (0.75 to 2.5 mm²) solid or stranded wire, which covers the typical control-circuit gauge for transformer primaries up to about 7.5 kVA.

Minimum clearances: 50 mm above and below, 30 mm to the side, and zero clearance forward or backward — meaning you can butt it against a back panel or enclosure wall without derating.

Frequently asked questions

What is 3RV2411-1DA15's depth and width?

Depth is 97 mm, width is 45 mm, height is 97 mm — the same compact 45 mm footprint as standard SIRIUS 3RV2 motor-protective breakers, so it fits existing panel layouts without re-spacing.

Will 3RV2411-1DA15 drop into a panel specified for 3RV2021-1FA15?

Both share the same 45 mm width and DIN rail mounting, so the physical fit is the same. The 3RV2411-1DA15 is designed for transformer protection with a different trip curve than the 3RV2021-1FA15 motor-protective breaker — verify the trip characteristics match your load before swapping.

MPN
3RV2411-1DA15