Skip to main content
Siemens 3RV2411-1EA10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2411-1EA10 SIRIUS Circuit Breaker, 100 kA at 400

MPN3RV2411-1EA10
Active

Siemens SIRIUS 3RV2411-1EA10 circuit breaker for transformer protection, 100 kA breaking capacity at 400 V, Trip Class 10, 45 mm wide, screw and snap-on 35 mm DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RV2411-1EA10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV2411-1EA10 — Electrical
ParameterValue
Rated operational current (Ie)4 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W
3RV2411-1EA10 — Protection & Tripping
ParameterValue
Overload release setting range2.8 ... 4 A
Instantaneous short-circuit trip current82 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)6 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V4 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2411-1EA10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0
3RV2411-1EA10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0,75 ... 2,5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (18 ... 14), 2x 12
3RV2411-1EA10 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2411-1EA10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2411-1EA10 — Specifications
ParameterValue
Design Of The ProductFor transformer protection

Product details

The Siemens 3RV2411-1EA10 is a SIRIUS circuit breaker specifically designed for transformer protection — not a general-purpose motor protective breaker. At 690 V it still clears 4 kA, covering the high-voltage end of the range. Fuse backup coordination is specified: gL/gG 32 A at 400 V and 500 V, derating to 25 A at 690 V. That tells the panel builder exactly what upstream fuse holds selectivity.

The 45 mm width fits a standard 2.5-module slot; depth is 97 mm, which clears most 100 mm-deep enclosures. Any mounting position is permitted, so vertical or horizontal rail orientation works. That keeps heat dissipation from derating the trip curve when multiple breakers are ganged. Main circuit terminals accept 2× (0.75 to 2.5 mm²) solid or stranded, or a single 4 mm² — screw-type terminals with M3 contact screws. Wire the line and load sides to the same torque spec.

Environmental and operating limits

Operates from -20 °C to +60 °C, stores and ships from -50 °C to +80 °C. That covers most plant-floor and warehouse conditions without special derating. Rated operating voltage spans 20 to 690 V AC.

MPN
3RV2411-1EA10