Skip to main content
Siemens 3RV2411-1EA20-0DA0 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2411-1EA20-0DA0 SIRIUS Circuit Breaker, S00, CLAS

MPN3RV2411-1EA20-0DA0
Active

Siemens SIRIUS 3RV2411-1EA20-0DA0, circuit breaker for transformer protection, size S00, CLASS 10 trip class, 100 kA breaking capacity at 400 V AC, screw and snap-on mounting on 35 mm DIN rail.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV2411-1EA20-0DA0 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00

Electrical

3RV2411-1EA20-0DA0 — Electrical
ParameterValue
Rated operational current (Ie)4 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W

Protection & Tripping

3RV2411-1EA20-0DA0 — Protection & Tripping
ParameterValue
Overload release setting range0.7 ... 1 A
Instantaneous short-circuit trip current82 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)6 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V4 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionNo
Ground-fault detectionNo
Auxiliary switch extendableYes

Endurance & Switching

3RV2411-1EA20-0DA0 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0

Connections

3RV2411-1EA20-0DA0 — Connections
ParameterValue
Main-circuit terminal typespring-loaded terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0,5 ... 4 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 2.5 mm²)

Mechanical

3RV2411-1EA20-0DA0 — Mechanical
ParameterValue
Height106 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
Mounting positionany

Environmental

3RV2411-1EA20-0DA0 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m

Specifications

3RV2411-1EA20-0DA0 — Specifications
ParameterValue
Design Of The ProductFor transformer protection

Product details

What it is and where it fits

The Siemens 3RV2411-1EA20-0DA0 is a SIRIUS circuit breaker specifically designed for transformer protection, size S00. It snaps onto a 35 mm DIN rail per DIN EN 60715 and accepts spring-loaded terminals on the main current circuit. The CLASS 10 trip class means it will hold through a transformer inrush and still trip on a hard fault — that's the right curve for a dry-type or small cast-coil unit feeding a control panel.

Breaking capacity and backup protection

Rated breaking capacity hits 100 kA at 240 V, 400 V, and 500 V AC; at 690 V it drops to 6 kA AC. That 100 kA at 400 V is the number your SCCR study needs — it means this breaker can interrupt a bolted fault up to that level without welding its contacts or venting arc gas into the enclosure. For backup protection, the manufacturer specifies gG fuse ratings: 32 A at 400 V and 500 V, 25 A at 690 V. If you're coordinating with an upstream fuse, those are the maximums the breaker relies on for its rated short-circuit performance.

Mounting and clearances

Fastens by screw or snap-on onto 35 mm rail. Mounting position is any, which simplifies panel layout. Required clearances: 50 mm above and below, 30 mm to the side, zero forward or backward. The 45 mm width and 97 mm depth mean it fits a standard 45 mm slot on a DIN rail — no overhang into the next position. Ambient operating range is -20 to +60 °C; storage and transport tolerate -50 to +80 °C.

Frequently asked questions

How do I get current pricing and availability for 3RV2411-1EA20-0DA0?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through independent distribution channels.

What is the breaking capacity of 3RV2411-1EA20-0DA0 at 400 V?

Rated breaking capacity is 100 kA at 400 V AC. At 690 V AC it is 6 kA.

What trip class does this circuit breaker have?

Trip class is CLASS 10, meaning it will hold through transformer inrush current and still trip on a sustained overload within 10 seconds at 7.2× the thermal setting.

MPN
3RV2411-1EA20-0DA0