Transformer-protection circuit breaker, Size S0
It carries a 100 kA short-circuit breaking capacity at 400 V AC (also at 240 V, 500 V, and 690 V AC), which means it can safely interrupt faults up to that level without cascading upstream. Trip Class 10 means the bimetal releases within 10 seconds at 7.2× the thermal setting — standard for protecting transformers against sustained overloads without nuisance tripping on inrush.
Size S0 frame, 45 mm wide, 97 mm deep, 97 mm tall. The 45 mm width means it occupies one standard modular slot; plan for 50 mm clearance above and below for wiring access, and 30 mm to the sides for heat dissipation. Screw-type terminals on the main circuit accept 2×(1…2.5 mm²) or 2×(2.5…10 mm²) solid or stranded copper.