The 3RV2421-0GA10 measures 97 mm deep, 45 mm wide, and 97 mm tall. The screw-type terminals on the main current circuit accept 2x 1 to 2.5 mm² solid or stranded, or 2x 2.5 to 10 mm², with an M4 screw for the main contacts. Screwdriver shaft diameter 5 to 6 mm.
This breaker delivers 100 kA breaking capacity at 240 V, 400 V, 500 V, and 690 V AC — that's a flat 100 kA curve across the common industrial voltages, not a derated number at the high end. At 230 V rated value it's specced at 0.1 kW, at 480 V and 600 V rated value it's 0.63 A — those are the transformer protection coordination points, not the breaker's own rating. The gL/gG fuse backup at 690 V is 6 A.