At 230 V it jumps to 100 kA, so it handles high-fault panels on the low-voltage side. The gL/gG fuse coordination limits are 63 A at 400 V, 50 A at 500 V, and 40 A at 690 V; if you're coordinating with upstream fuses, those are the max values for selective isolation.
Terminals and wiring
Screw-type terminals on the main circuit accept 2x (1 to 2.5 mm²) or 2x (2.5 to 10 mm²) solid or stranded copper. M4 terminal screws — torque them to the standard panel value for that size. No ground-fault detection onboard, but it does include phase-failure detection, so if one phase drops out on a three-phase transformer, the breaker trips.