Skip to main content
Siemens 3RV2421-4AA15 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2421-4AA15 SIRIUS Circuit Breaker, Transformer Pr

MPN3RV2421-4AA15
Active

Siemens SIRIUS circuit breaker, 3RV2421-4AA15, for transformer protection, 25 kA breaking capacity at 400 V, Trip Class 10, phase failure detection, screw and snap-on mounting onto 35 mm DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RV2421-4AA15 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS0
3RV2421-4AA15 — Electrical
ParameterValue
Rated operational current (Ie)16 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)9.25 W
Power loss, per pole (AC, hot)3.1 W
3RV2421-4AA15 — Protection & Tripping
ParameterValue
Overload release setting range10 ... 16 A
Instantaneous short-circuit trip current286 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)55 kA
Breaking capacity at 500 V (AC)10 kA
Breaking capacity at 690 V (AC)4 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V2 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2421-4AA15 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0
3RV2421-4AA15 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (16 ... 12), 2x (14 ... 8)
3RV2421-4AA15 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2421-4AA15 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2421-4AA15 — Specifications
ParameterValue
Design Of The ProductFor transformer protection

Product details

Transformer-protection circuit breaker from the SIRIUS family

The Siemens 3RV2421-4AA15 is a SIRIUS-brand circuit breaker specifically designed for transformer protection, not general motor or feeder duty. It carries a Trip Class 10 rating and includes phase failure detection, which means it will trip on loss of a phase — a common failure mode in transformer-fed loads that can cause single-phasing damage downstream. Breaking capacity is 25 kA at 400 V, with a rated operational voltage range of 20 to 690 V.

Coordination and selectivity notes

Rated for gL/gG fuse backup at 63 A (400 V), 50 A (500 V), and 40 A (690 V). If you are coordinating this breaker downstream of a larger fuse or MCCB, those are the maximum upstream fuse ratings that maintain selectivity under short-circuit conditions. The 100 kA rated short-circuit capacity at 240 V applies only with the specified upstream fuse — without it, the 25 kA at 400 V is the standalone interrupting rating.

Main contact terminals accept M4 screws. Wire capacity is 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid or stranded.

Frequently asked questions

What is the breaking capacity of 3RV2421-4AA15 at 400 V?

25 kA at 400 V. At 690 V the rating is 2 kA, and at 240 V with specified upstream fuse it reaches 100 kA.

What does Trip Class 10 mean for this breaker?

Trip Class 10 means the overload relay element will trip within 10 seconds at 7.2× the thermal setting. This is standard for transformer protection where inrush can be high but sustained overloads must clear quickly.

Where can I buy the 3RV2421-4AA15?

This part is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time, not from a live stock count.

MPN
3RV2421-4AA15