It sits in the main current circuit, sized to handle inrush without nuisance tripping thanks to its Class 10 trip characteristic.
Breaking capacity — the real number that matters
At 240 V AC this breaker interrupts 100 kA. At 400 V AC it still handles 65 kA. That's enough for most industrial service-entrance panels and transformer secondaries. The 480 V rating is 36 A continuous, which matches the typical secondary of a 30 kVA transformer.
The footprint is 55 mm wide, 140 mm tall, 149 mm deep. Clearances: 50 mm above and below, 10 mm to the side, zero forward or backward.